type


TEST PERFORMED STANDARD REFERENCE CERTIFICATION AUTORITY CERTIFICATE REFERENCE
Short-circuit withstand strength (Icw= 70kA-1s) CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.11.5.3.1 / 10.11.5.3.3 / 10.11.5.3.5 / 10.11.5.6 ] LOVAG /
Temperature-rise limits (Verification of the complete assembly) CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.10.2.3.5 ] LOVAG /
Clearances and creepage distances CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.4 ] LOVAG /
Protection against electric shock and integrity of protective circuits CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.5 ] LOVAG /
Dielectric properties (Power-frequency withstand voltage) CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.9.2 ] LOVAG /
Dielectric properties (Impulse withstand voltage) CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.9.3.2 ] LOVAG /
Mechanical strength/operation CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.13 ] LOVAG /
Strength of materials and parts (Resistance to corrosion) CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.2.2 ] LOVAG
Lifting provision CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.2.5 ] LOVAG
Protection against mechanical impact CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.2.6 ] LOVAG
Degree of protection CEI EN 61439-1 / CEI EN 61439-2 (IEC 61439-1 / 61439-2) [ par. 10.3 ] LOVAG
Internal Arc Fault Test Inside IEC/TR 61641: 2008-01 IPH Berlin 00857-14-0307